5 SETTINGS
5.7 CONTROL ELEMENTS
5
•
I
B
= protected element base (nominal) current
To ensure element accuracy for high overcurrent conditions, the maximum value of I/(k x I
B
) is limited to 8, even when real-
istically it is exceeding this value.
The reset time of the thermal overload protection element is also time delayed using following formula:
(EQ 5.52)
In the above equation,
•
τ
rst
= thermal protection trip time constant
•
T
min
is a minimum reset time setting
Figure 5–156: IEC 255-8 SAMPLE OPERATE AND RESET CURVES
The thermal overload protection element estimates accumulated thermal energy
E
using the following equations calculated
each power cycle. When current is greater than the pickup level,
I
n
>
k
×
I
B
, element starts increasing the thermal energy:
t
rst
τ
rst
kI
B
(
)
2
I
2
kI
B
(
)
2
–
-----------------------------
ln
×
T
min
+
=
0.1
1
10
100
I / Ipkp
t (min)
0.01
0.1
1
10
100
τ
= 30
rst
τ
= 30
op
T
= 10
min
827724A1.CDR
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...