B-90
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
F169
ENUMERATION: OVEREXCITATION INHIBIT FUNCTION
0 = Disabled, 1 = 5th
F172
ENUMERATION: SLOT LETTERS
F173
ENUMERATION: DCmA INPUT/OUTPUT RANGE
F174
ENUMERATION: TRANSDUCER RTD INPUT TYPE
0 = 100 Ohm Platinum, 1 = 120 Ohm Nickel,
2 = 100 Ohm Nickel, 3 = 10 Ohm Copper
F176
ENUMERATION: SYNCHROCHECK DEAD SOURCE SELECT
F177
ENUMERATION: COMMUNICATION PORT
0 = None, 1 = COM1-RS485 (not applicable to UR firmware 7.00),
2 = COM2-RS485, 3 = Front Panel-RS232, 4 = Network - TCP,
5 = Network - UDP
F183
ENUMERATION: AC INPUT WAVEFORMS
F184
ENUMERATION: IEC GOOSE DATASET
F186
ENUMERATION: MEASUREMENT MODE
0 = Phase to Ground, 1 = Phase to Phase
F189
ENUMERATION: INRUSH INHIBIT MODE
0 = Per Phase, 1 = 2-out-of-3, 2 = Average
Bitmas
k
Slot
Bitmas
k
Slot
Bitmas
k
Slot
Bitmas
k
Slot
0
F
4
K
8
P
12
U
1
G
5
L
9
R
13
V
2
H
6
M
10
S
14
W
3
J
7
N
11
T
15
X
Bitmask
DCmA input/output range
0
0 to –1 mA
1
0 to 1 mA
2
–1 to 1 mA
3
0 to 5 mA
4
0 to 10 mA
5
0 to 20 mA
6
4 to 20 mA
Bitmask
Synchrocheck dead source
0
None
1
LV1 and DV2
2
DV1 and LV2
3
DV1 or DV2
4
DV1 Xor DV2
5
DV1 and DV2
Bitmask
Definition
0
Off
1
8 samples/cycle
2
16 samples/cycle
3
32 samples/cycle
4
64 samples/cycle
Value
IEC 61850 dataset
0
Off
1
GooseIn 1
2
GooseIn 2
3
GooseIn 3
4
GooseIn 4
5
GooseIn 5
6
GooseIn 6
7
GooseIn 7
8
GooseIn 8
9
GooseIn 9
10
GooseIn 10
11
GooseIn 11
12
GooseIn 12
13
GooseIn 13
14
GooseIn 14
15
GooseIn 15
16
GooseIn 16
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...