B-42
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
5EA8
...Repeated for CT Fail 6
Setting Groups (Read/Write Setting)
5F70
Setting Group for Modbus Comms (0 means group 1)
0 to 5
---
1
F001
0
5F71
Setting Groups Block
0 to 4294967295
---
1
F300
0
5F73
FlexLogic Operands to Activate Groups 2 through 6 (5
items)
0 to 4294967295
---
1
F300
0
5F7D
Setting Group Function
0 to 1
---
1
F102
0 (Disabled)
5F7E
Setting Group Events
0 to 1
---
1
F102
0 (Disabled)
Setting Groups (Read Only)
5F7F
Current Setting Group
0 to 5
---
1
F001
0
Setting Group Names (Read/Write Setting)
5F8C
Setting Group 1 Name
---
---
---
F203
(none)
5F94
Setting Group 2 Name
---
---
---
F203
(none)
5F9C
Setting Group 3 Name
---
---
---
F203
(none)
5FA4
Setting Group 4 Name
---
---
---
F203
(none)
5FAC
Setting Group 5 Name
---
---
---
F203
(none)
5FB4
Setting Group 6 Name
---
---
---
F203
(none)
Transformer Hottest Spot (Read/Write Grouped Setting)
6140
Transformer Hottest Spot Function
0 to 1
---
1
F102
0 (Disabled)
6141
Transformer Hottest Spot Pickup
50 to 300
°C
1
F001
140
6142
Transformer Hottest Spot Delay
0 to 30000
min
1
F001
1
6143
Transformer Hottest Spot Block
0 to 4294967295
---
1
F300
0
6145
Transformer Hottest Spot Target
0 to 2
---
1
F109
0 (Self-reset)
6146
Transformer Hottest Spot Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Aging Factor (Read/Write Grouped Setting)
6150
Transformer Aging Factor Function
0 to 1
---
1
F102
0 (Disabled)
6151
Transformer Aging Factor Pickup
1 to 10
PU
0.1
F001
20
6152
Transformer Aging Factor Delay
0 to 30000
min
1
F001
10
6153
Transformer Aging Factor Block
0 to 4294967295
---
1
F300
0
6155
Transformer Aging Factor Target
0 to 2
---
1
F109
0 (Self-reset)
6156
Transformer Aging Factor Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Loss of Life (Read/Write Grouped Setting)
6160
Transformer Loss of Life Function
0 to 1
---
1
F102
0 (Disabled)
6161
XFMR LOL Initial Value
0 to 500000
hrs
1
F003
0
6163
Transformer Loss of Life Pickup
0 to 500000
hrs
1
F003
180000
6165
Transformer Loss Of Life Block
0 to 4294967295
---
1
F300
0
6167
Transformer Loss of Life Target
0 to 2
---
1
F109
0 (Self-reset)
6168
Transformer Loss of Life Events
0 to 1
---
1
F102
0 (Disabled)
Transformer Thermal Inputs (Read/Write Setting)
6170
Transformer Thermal Model Source Input
0 to 5
---
1
F167
0 (SRC 1)
6171
Ambient Temperature Input Sensor
0 to 32
---
1
F450
0
6172
Top Oil Temperature Input Sensor
0 to 32
---
1
F460
0
6173
January Average Ambient Temperature
-60 to 60
°C
1
F002
-20
6174
February Average Ambient Temperature
-60 to 60
°C
1
F002
-30
6175
March Average Ambient Temperature
-60 to 60
°C
1
F002
-10
6176
April Average Ambient Temperature
-60 to 60
°C
1
F002
10
6177
May Average Ambient Temperature
-60 to 60
°C
1
F002
20
6178
June Average Ambient Temperature
-60 to 60
°C
1
F002
30
6179
July Average Ambient Temperature
-60 to 60
°C
1
F002
30
617A
August Average Ambient Temperature
-60 to 60
°C
1
F002
30
617B
September Average Ambient Temperature
-60 to 60
°C
1
F002
20
617C
October Average Ambient Temperature
-60 to 60
°C
1
F002
10
617D
November Average Ambient Temperature
-60 to 60
°C
1
F002
10
617E
December Average Ambient Temperature
-60 to 60
°C
1
F002
-10
Table B–10: MODBUS MEMORY MAP (Sheet 34 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...