GE Multilin
T60 Transformer Protection System
B-43
APPENDIX B
B.4 MEMORY MAPPING
B
Transformer Thermal Inputs (Read/Write Command)
6180
Transformer Loss of Life Clear Command
0 to 1
---
1
F126
0 (No)
Transformer Percent Differential (Read/Write Grouped Setting)
61C0
Percent Differential Function
0 to 1
---
1
F102
0 (Disabled)
61C1
Percent Differential Pickup
0.05 to 1
pu
0.001
F001
100
61C2
Percent Differential Slope 1
15 to 100
%
1
F001
25
61C3
Percent Differential Break 1
1 to 2
pu
0.001
F001
2000
61C4
Percent Differential Break 2
2 to 30
pu
0.001
F001
8000
61C5
Percent Differential Slope 2
50 to 100
%
1
F001
100
61C6
Inrush Inhibit Function
0 to 2
---
1
F168
1 (Adapt. 2nd)
61C7
Inrush Inhibit Level
1 to 40
%fo
0.1
F001
200
61C8
Overexcitation Inhibit Function
0 to 1
---
1
F169
0 (Disabled)
61C9
Overexcitation Inhibit Level
1 to 40
%fo
0.1
F001
100
61CA
Percent Differential Block
0 to 4294967295
---
1
F300
0
61CC
Percent Differential Target
0 to 2
---
1
F109
0 (Self-reset)
61CD
Percent Differential Events
0 to 1
---
1
F102
0 (Disabled)
61CE
Transformer Inrush Inhibit Mode
0 to 2
---
1
F189
0 (Per phase)
Transformer Instantaneous Differential (Read/Write Grouped Setting)
61DA
Inst Differential Function
0 to 1
---
1
F102
0 (Disabled)
61DB
Inst Differential Pickup
2 to 30
pu
0.001
F001
8000
61DC
Inst Differential Block
0 to 4294967295
---
1
F300
0
61DE
Inst Differential Target
0 to 2
---
1
F109
0 (Self-reset)
61DF
Inst Differential Events
0 to 1
---
1
F102
0 (Disabled)
Overfrequency (Read/Write Setting) (4 modules)
6470
Overfrequency 1 Function
0 to 1
---
1
F102
0 (Disabled)
6471
Overfrequency 1 Block
0 to 4294967295
---
1
F300
0
6473
Overfrequency 1 Source
0 to 5
---
1
F167
0 (SRC 1)
6474
Overfrequency 1 Pickup
20 to 65
Hz
0.01
F001
6050
6475
Overfrequency 1 Pickup Delay
0 to 65.535
s
0.001
F001
500
6476
Overfrequency 1 Reset Delay
0 to 65.535
s
0.001
F001
500
6477
Overfrequency 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6478
Overfrequency 1 Events
0 to 1
---
1
F102
0 (Disabled)
6479
Reserved (4 items)
0 to 1
---
1
F001
0
647D
...Repeated for Overfrequency 2
648A
...Repeated for Overfrequency 3
6497
...Repeated for Overfrequency 4
Power Swing Detect (Read/Write Grouped Setting)
65C0
Power Swing Detect Function
0 to 1
---
1
F102
0 (Disabled)
65C1
Power Swing Detect Source
0 to 5
---
1
F167
0 (SRC 1)
65C2
Power Swing Detect Mode
0 to 1
---
1
F513
0 (Two Step)
65C3
Power Swing Detect Supervision
0.05 to 30
pu
0.001
F001
600
65C4
Power Swing Detect Forward Reach
0.1 to 500
ohms
0.01
F001
5000
65C5
Power Swing Detect Forward RCA
40 to 90
degrees
1
F001
75
65C6
Power Swing Detect Reverse Reach
0.1 to 500
ohms
0.01
F001
5000
65C7
Power Swing Detect Reverse RCA
40 to 90
degrees
1
F001
75
65C8
Power Swing Detect Outer Limit Angle
40 to 140
degrees
1
F001
120
65C9
Power Swing Detect Middle Limit Angle
40 to 140
degrees
1
F001
90
65CA
Power Swing Detect Inner Limit Angle
40 to 140
degrees
1
F001
60
65CB
Power Swing Detect Delay 1 Pickup
0 to 65.535
s
0.001
F001
30
65CC
Power Swing Detect Delay 1 Reset
0 to 65.535
s
0.001
F001
50
65CD
Power Swing Detect Delay 2 Pickup
0 to 65.535
s
0.001
F001
17
65CE
Power Swing Detect Delay 3 Pickup
0 to 65.535
s
0.001
F001
9
65CF
Power Swing Detect Delay 4 Pickup
0 to 65.535
s
0.001
F001
17
65D0
Power Swing Detect Seal In Delay
0 to 65.535
s
0.001
F001
400
Table B–10: MODBUS MEMORY MAP (Sheet 35 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...