B-78
T60 Transformer Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
D764
...Repeated for Contact Output 61
D773
...Repeated for Contact Output 62
D782
...Repeated for Contact Output 63
D791
...Repeated for Contact Output 64
DCmA Inputs (Read/Write Setting) (24 modules)
D7A0
DCmA Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
D7A1
DCmA Inputs 1 ID
---
---
---
F205
“DCMA Ip 1"
D7A7
Reserved 1 (4 items)
0 to 65535
---
1
F001
0
D7AB
DCmA Inputs 1 Units
---
---
---
F206
“mA”
D7AE
DCmA Inputs 1 Range
0 to 6
---
1
F173
6 (4 to 20 mA)
D7AF
DCmA Inputs 1 Minimum Value
-9999.999 to 9999.999
---
0.001
F004
4000
D7B1
DCmA Inputs 1 Maximum Value
-9999.999 to 9999.999
---
0.001
F004
20000
D7B3
...Repeated for DCmA Inputs 2
D7C6
...Repeated for DCmA Inputs 3
D7D9
...Repeated for DCmA Inputs 4
D7EC
...Repeated for DCmA Inputs 5
D7FF
...Repeated for DCmA Inputs 6
D812
...Repeated for DCmA Inputs 7
D825
...Repeated for DCmA Inputs 8
D838
...Repeated for DCmA Inputs 9
D84B
...Repeated for DCmA Inputs 10
D85E
...Repeated for DCmA Inputs 11
D871
...Repeated for DCmA Inputs 12
D884
...Repeated for DCmA Inputs 13
D897
...Repeated for DCmA Inputs 14
D8AA
...Repeated for DCmA Inputs 15
D8BD
...Repeated for DCmA Inputs 16
D8D0
...Repeated for DCmA Inputs 17
D8E3
...Repeated for DCmA Inputs 18
D8F6
...Repeated for DCmA Inputs 19
D909
...Repeated for DCmA Inputs 20
D91C
...Repeated for DCmA Inputs 21
D92F
...Repeated for DCmA Inputs 22
D942
...Repeated for DCmA Inputs 23
D955
...Repeated for DCmA Inputs 24
DNP/IEC Points (Read/Write Setting)
D968
DNP/IEC 60870-5-104 Binary Input Points (256 items)
0 to 4294967295
---
1
F300
0
DB68
DNP/IEC 60870-5-104 Analog Input Points (256 items)
0 to 65535
---
1
F600
0
Synchrocheck (Read/Write Setting) (4 modules)
DC70
Synchrocheck 1 Function
0 to 1
---
1
F102
0 (Disabled)
DC71
Synchrocheck 1 V1 Source
0 to 5
---
1
F167
0 (SRC 1)
DC72
Synchrocheck 1 V2 Source
0 to 5
---
1
F167
1 (SRC 2)
DC73
Synchrocheck 1 Maximum Voltage Difference
0 to 400000
V
1
F060
10000
DC75
Synchrocheck 1 Maximum Angle Difference
0 to 100
degrees
1
F001
30
DC76
Synchrocheck 1 Maximum Frequency Difference
0 to 2
Hz
0.01
F001
100
DC77
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
DC78
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
DC79
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
DC7A
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
DC7B
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
DC7C
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
DC7D
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
DC7E
Synchrocheck 1 Block
0 to 4294967295
---
1
F300
0
DC80
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
Table B–10: MODBUS MEMORY MAP (Sheet 70 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...