![background image](http://html.mh-extra.com/html/ge/t60/t60_instruction-manual_123344643.webp)
GE Multilin
T60 Transformer Protection System
B-47
APPENDIX B
B.4 MEMORY MAPPING
B
74A5
Disconnect Switch 1 Open
0 to 4294967295
---
1
F300
0
74A7
Disconnect Switch 1 Block Open
0 to 4294967295
---
1
F300
0
74A9
Disconnect Switch 1 Close
0 to 4294967295
---
1
F300
0
74AB
Disconnect Switch 1 Block Close
0 to 4294967295
---
1
F300
0
74AD
Disconnect Switch 1 Phase A / Three-pole Closed
0 to 4294967295
---
1
F300
0
74AF
Disconnect Switch 1 Phase A / Three-pole Opened
0 to 4294967295
---
1
F300
0
74B1
Disconnect Switch 1 Phase B Closed
0 to 4294967295
---
1
F300
0
74B3
Disconnect Switch 1 Phase B Opened
0 to 4294967295
---
1
F300
0
74B5
Disconnect Switch 1 Phase C Closed
0 to 4294967295
---
1
F300
0
74B7
Disconnect Switch 1 Phase C Opened
0 to 4294967295
---
1
F300
0
74B9
Disconnect Switch 1 Operate Time
0 to 65.535
s
0.001
F001
70
74BA
Disconnect Switch 1 Alarm Delay
0 to 65.535
s
0.001
F003
0
74BC
Disconnect Switch 1 Events
0 to 1
---
1
F102
0 (Disabled)
74BD
Reserved (2 items)
---
---
---
F001
0
74BF
...Repeated for Disconnect Switch 2
74DE
...Repeated for Disconnect Switch 3
74FD
...Repeated for Disconnect Switch 4
751C
...Repeated for Disconnect Switch 5
753B
...Repeated for Disconnect Switch 6
755A
...Repeated for Disconnect Switch 7
7579
...Repeated for Disconnect Switch 8
7598
...Repeated for Disconnect Switch 9
75B7
...Repeated for Disconnect Switch 10
75D6
...Repeated for Disconnect Switch 11
75F5
...Repeated for Disconnect Switch 12
7614
...Repeated for Disconnect Switch 13
7633
...Repeated for Disconnect Switch 14
7652
...Repeated for Disconnect Switch 15
7671
...Repeated for Disconnect Switch 16
7690
...Repeated for Disconnect Switch 17
76AF
...Repeated for Disconnect Switch 18
76CE
...Repeated for Disconnect Switch 19
76ED
...Repeated for Disconnect Switch 20
770C
...Repeated for Disconnect Switch 21
772B
...Repeated for Disconnect Switch 22
774A
...Repeated for Disconnect Switch 23
7769
...Repeated for Disconnect Switch 24
Thermal Overload Protection (Read/Write Settings) (2 modules)
7788
Thermal Protection 1 Function
0 to 1
---
1
F102
0 (Disabled)
7789
Thermal Protection 1 Source
0 to 5
---
1
F167
0 (SRC 1)
778A
Thermal Protection 1 Base Current
0.2 to 3
pu
0.01
F001
80
778B
Thermal Protection 1 K Factor
1 to 1.2
---
0.05
F001
110
778C
Thermal Protection 1 Trip Time Constant
0 to 1000
min.
1
F001
45
778D
Thermal Protection 1 Reset Time Constant
0 to 1000
min.
1
F001
45
778E
Thermal Protection 1 Minimum Reset Time
0 to 1000
min.
1
F001
20
778F
Thermal Protection 1 Reset
0 to 4294967295
---
1
F300
0
7791
Thermal Protection 1 Block
0 to 4294967295
---
1
F300
0
7793
Thermal Protection 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7794
Thermal Protection 1 Events
0 to 1
---
1
F102
0 (Disabled)
7795
Reserved (2 items)
---
---
---
F001
0
7797
Repeated for Thermal Protection 2
Ohm Inputs (Read/Write Setting) (2 modules)
77F8
Ohm Inputs 1 Function
0 to 1
---
1
F102
0 (Disabled)
77F9
Ohm Inputs 1 ID
---
---
---
F205
"Ohm Ip 1 "
Table B–10: MODBUS MEMORY MAP (Sheet 39 of 73)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...