GE Multilin
T60 Transformer Protection System
5-87
5 SETTINGS
5.2 PRODUCT SETUP
5
•
PUSHBTN 1 MESSAGE
: This setting controls the behavior of the user-programmable pushbutton that is programmed
in the
PUSHBTN 1 ID
and
PUSHBTN 1 ON TEXT
settings, and the behavior of the user-programmable pushbutton off mes-
sage that is programmed in the
PUSHBTN1 ID
and
PUSHBTN 1 OFF TEXT
settings.
When set to "Disabled", user-programmable pushbutton messages do not display. Otherwise the on message displays
when the user-programmable pushbutton becomes activated, and if in the "Latched" mode the off message displays
when the user-programmable pushbutton becomes deactivated.
When set to "Normal", the duration the message displays is as specified by the
FLASH MESSAGE TIME
setting.
When set to "High Priority", the duration of the off message is as specified by the
FLASH MESSAGE TIME
setting, but the
on message is displayed as long as the user-programmable pushbutton is activated. While activated, target and other
messages are suppressed. To allow front panel keypad operation, when a keypad button is pressed the message is
supressed for 10 seconds.
•
PUSHBUTTON 1 EVENTS
: If this setting is enabled, each user-programmable pushbutton state change is logged as
an event into the event recorder.
The figures show the user-programmable pushbutton logic.
Figure 5–16: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 1 of 2)
S
R
Non-volatile latch
Latch
OR
OR
OR
OR
AND
SETTING
= Enabled
= Latched
PUSHBUTTON 1 FUNCTION
= Self-Reset
SETTING
Off = 0
PUSHBTN 1 LOCAL
SETTING
Off = 0
PUSHBTN 1 SET
SETTING
Off = 0
PUSHBTN 1 RESET
SETTING
= Enabled
= Disabled
PUSHBTN 1 AUTORST
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
AND
AND
AND
AND
TIMER
50 ms
0
TIMER
50 ms
0
TIMER
200 ms
0
AND
SETTING
PUSHBTN 1 DROP-OUT TIME
T
RST
0
PUSHBUTTON ON
To user-programmable
pushbuttons logic
sheet 2
LATCHED
From front panel
To user-programmable
pushbuttons logic
sheet 2
842021A4.CDR
SETTING
PUSHBTN 1 AUTORST DELAY
T
PKP
0
From front panel
SETTING
PUSHBTN 1 HOLD
T
PKP
0
SETTING
Off = 0
PUSHBTN 1 REMOTE
AND
SETTING
PUSHBUTTON 1 OFF
TIMER
200 ms
0
OR
AND
OR
AND
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...