GE Multilin
T60 Transformer Protection System
5-201
5 SETTINGS
5.6 GROUPED ELEMENTS
5
Figure 5–88: GROUND DIRECTIONAL SUPERVISION SCHEME LOGIC
5.6.4 POWER SWING DETECT (ANSI 68)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
POWER SWING DETECT
POWER SWING
DETECT
POWER SWING
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
POWER SWING
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
MESSAGE
POWER SWING
SHAPE: Mho Shape
Range: Mho Shape, Quad Shape
MESSAGE
POWER SWING
MODE: Two Step
Range: Two Step, Three Step
MESSAGE
POWER SWING
SUPV: 0.600 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SW I2 SUPV ENAB:
Off
Range: FlexLogic operand
MESSAGE
POWER SWING
I2 SUPV: 0.2 pu
Range: 0.050 to 30.000 pu in steps of 0.001
MESSAGE
POWER SWING FWD
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD FWD
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING FWD
RCA: 75°
Range: 40 to 90° in steps of 1
MESSAGE
POWER SWING REV
REACH: 50.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH MID: 60.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING QUAD REV
REACH OUT: 70.00
Ω
Range: 0.10 to 500.00 ohms in steps of 0.01
MESSAGE
POWER SWING REV
RCA: 75°
Range: 40 to 90° in steps of 1
V_0 > 5 volts
RUN
Zero-sequence
directional characteristic
837009A7.CDR
AND
OR
Co-ordinating time:
pickup = 1.0 cycle, reset = 1.0 cycle
SETTING
= V_0
= I_0
Distance Source
FLEXLOGIC OPERAND
OPEN POLE OP
TIMER
t
pickup
t
reset
FLEXLOGIC OPERAND
GND DIST Z2 DIR SUPN
Summary of Contents for T60
Page 6: ...vi T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 14: ...xiv T60 Transformer Protection System GE Multilin TABLE OF CONTENTS ...
Page 34: ...1 20 T60 Transformer Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Page 490: ...5 344 T60 Transformer Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Page 522: ...6 32 T60 Transformer Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Page 536: ...7 14 T60 Transformer Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Page 568: ...10 12 T60 Transformer Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Page 596: ...A 28 T60 Transformer Protection System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Page 716: ...B 120 T60 Transformer Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Page 762: ...E 10 T60 Transformer Protection System GE Multilin E 1 IEC 60870 5 104 PROTOCOL APPENDIX E E ...
Page 774: ...F 12 T60 Transformer Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...