Troubleshooting by Error Code
SiUS342004EB
351
Part 6 Service Diagnosis
Reference
CHECK 15
Refer to page 370.
Check the
transmission
wiring
b
etween
centralized controller for
any
b
roken wire.
Is the
v
oltage
b
etween the
terminals F1 (+) and F2 (-)
in the range of 15.2
to 17.6 VDC?
Check the
transmission wiring
b
etween main centralized
controller for any
b
roken wire.
Replace the centralized
controller.
Centralized controller: Normal
OK
Correct the wiring.
NG
A
NO
Correct the wiring.
NG
YES
YES
Disconnect the transmission
wiring of the main centralized
controller, and then check the
v
oltage
b
etween the
transmission terminals (F1 and
F2) of the master
u
nit
transmission e
qu
ipment
u
sing
a m
u
ltimeter.
It is s
u
pposed that the error
res
u
lts from external factors
(e.g. noises) from other
e
qu
ipment.
CHECK 15
CHECK 15
Has the
main centralized
controller setting connector
b
een connected?
OK
Correct the connection of the
connector.
NO
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...