SiUS342004EB
Outline of Control (Indoor Unit)
Part 4 Functions and Control
114
9.4.2 With Infrared Floor Sensor
Whether the thermostat is turned on or off is determined by the difference between the remote
controller set temperature and the detected temperature around people.
Normal operation
Cooling operation
Heating operation
Dry operation
When Tro ≤ 24.5°C (76.1°F)
When Tro > 24.5°C (76.1°F)
FXFQ-AA, FXZQ-TB, FXUQ-PA only
If the field setting 11 (21)-12 is set to
02
, Tro will be the same as the cooling set temperature.
ΔT = Room temperature or temperature around people – Remote controller set temperature
Tro: Room temperature or temperature around people at the start of dry operation
Tr: Room temperature or temperature around people
Control range of
temperature
around people
When the floor temperature is very low, operation using the temperature around people may cause
the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use range of
the temperature around people.
Cooling operation
When the floor temperature is lower than suction air temperature (R1T), R1T will be treated as
the control target temperature for operation.
When the temperature around people is 15°C (59°F) or lower, R1T will be treated as the control
temperature for operation.
Heating operation
When the floor temperature is higher than suction air temperature (R1T), R1T will be treated as
the control target temperature in operation.
When the temperature around people is 33°C (91.4°F) or higher, R1T will be treated as the
control temperature for operation.
Thermostat OFF
N
ormal operation
(Thermostat O
N
)
Δ
T
≤
–1.0˚C (–1.
8
˚F)
Δ
T
≥ +
1.0˚C (
+
1.
8
˚F)
Thermostat OFF
N
ormal operation
(Thermostat O
N
)
Δ
T
≥ +
1.0˚C (
+
1.
8
˚F)
Δ
T
≤
–1.0˚C (–1.
8
˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0˚C (– 1.
8
˚F)
Tr > Tro + 1.0˚C (+ 1.
8
˚F)
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5˚C (– 2.7˚F)
Tr > Tro + 0.5˚C (+ 0.9˚F)
Thermostat OFF
Dry operation
Tr < Tro – 1.0˚C (–1.8˚F)
Tr
>
Tro + 1.0˚C (
+
1.8˚F)
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...