SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
316
Reference
CHECK 4
Refer to page 362.
CHECK 4
Is the power
transistor normal?
YES
Recheck for the compressor and the
refrigerant system.
NO
Replace the inverter PCB (A4P).
NO
YES
NO
The internal
wiring of the
compressor coil is
defective
Replace the compressor.
YES
Is the
insulation
resistance of the
relevant compressor
100 k
Ω
or more?
Refrigerant is
stagnated. (The unit is out
of power supply for more
than 6 hours.)
Replace the compressor.
NO
Solve the refrigerant stagnation.
(Power should be supplied for more
than 6 hours.)
YES
A