Troubleshooting by Error Code
SiUS342004EB
291
Part 6 Service Diagnosis
3.38 Outdoor Fan Motor Abnormality
Applicable
Models
All outdoor unit models
Error Code
E7
Method of Error
Detection
Detects according to the value of current flowing through the fan PCB.
Error Decision
Conditions
Overcurrent is detected from the fan PCB (Detecting overcurrent 4 times will shut down the
system).
Current does not increase at fan motor startup or while the fan motor is in operation (Detecting 4
times will shut down the system).
Supposed
Causes
Fan motor failure
Neglect to connect or defective connection of harness/connector between the fan motor and the
PCB
Fan does not rotate due to foreign matter caught in it.
Clearing condition: fan motor performs normal operation for a period of 5 minutes