Troubleshooting by Error Code
SiUS342004EB
285
Part 6 Service Diagnosis
Reference
Reference
CHECK 1
Refer to page 357.
CHECK 12
Refer to page 369.
Replace the outdoor unit
main PCB (A1P).
NO
YES
Are both
pressure values
the
same?
-The high pressure sensor is normal, and outdoor unit main PCB is also
normal.
-The high pressure has really become high.
CHECK 1
: Eliminate factors that cause the high pressure to rise.
Connect the service checker, and then compare the high pressure value
measured by the service checker with the voltage measurement of the
connector of the pressure sensor (
1)
Service Checker
CHECK 12
A
Replace the high pressure sensor
(S1NPH).
NO
Compare the
voltage
measurement of the
connector of the pressure
sensor (
1) with the
measurement of the pressure
gauge. Are the
characteristics of the
high pressure
sensor
normal?
CHECK 12
YES
(
1)
Use the ta
b
le on
CHECK 12
to
con
v
ert the
v
oltage meas
u
rement into
press
u
re meas
u
rement.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...