SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
160
1. FXMQ54TB cannot be set to 150-200 Pa (0.60-0.80 inWG).
FXMQ-TB models
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
02
50 Pa (0.20 inWG)
03
60 Pa (0.24 inWG)
04
70 Pa (0.28 inWG)
05
80 Pa (0.32 inWG)
06
90 Pa (0.36 inWG)
07
100 Pa (0.40 inWG)
08
110 Pa (0.44 inWG)
09
120 Pa (0.48 inWG)
10
130 Pa (0.52 inWG)
11
140 Pa (0.56 inWG)
12
150 Pa (0.60 inWG) (
1)
13
160 Pa (0.64 inWG) (
1)
14
180 Pa (0.72 inWG) (
1)
15
200 Pa (0.80 inWG) (
1)
FXMQ-TA models
: Factory setting
Mode No.
First Code No.
Second Code No.
Contents
13 (23)
6
01
50 Pa (0.20 inWG)
02
75 Pa (0.30 inWG)
03
100 Pa (0.40 inWG)
04
115 Pa (0.46 inWG)
05
130 Pa (0.52 inWG)
06
150 Pa (0.60 inWG)
07
160 Pa (0.64 inWG)
08
175 Pa (0.70 inWG)
09
190 Pa (0.76 inWG)
10
200 Pa (0.80 inWG)
11
210 Pa (0.84 inWG)
12
220 Pa (0.88 inWG)
13
230 Pa (0.92 inWG)
14
240 Pa (0.96 inWG)
15
250 Pa (1.00 inWG)
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...