Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
138
1.1.3 Wireless Remote Controller
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
To change the field settings, proceed as follows:
1. Press the
INSPECTION/TEST
button for 4 seconds during normal mode to enter the field
setting mode.
2. Press the
MODE
button to select the desired mode No.
3. Press the
UP
button to select the first code No.
4. Press the
DOWN
button to select the second code No.
5. Press the
RESERVE
button to confirm the setting.
6. Press the
INSPECTION/TEST
button to return to the normal mode.
RESERVE
button
INSPECTION/TEST
button
Mode
N
o.
Field setting mode
UP
button
DOWN
button
First code
N
o.
Second code
N
o.
MODE
button
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...