SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
166
1.6 List of Field Settings for Outdoor-Air Processing Unit
: Factory setting
1.7 Operation Control Mode
The operation control mode is compatible with a variety of controls and operations by limiting the
functions of the operation remote controller. Furthermore, operations such as remote controller
ON/OFF can be limited in accordance with the combination conditions. (Refer to information on the
next page.)
Central remote controller is normally available for operations. (Except when centralized monitor is
connected)
20 modes consisting of combinations of the following 5 operation modes with temperature and
operation mode setting by remote controller can be set and displayed by operation modes 0
through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only. (Cannot be turned
ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller
only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by
remote controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want
to start operation by central remote controller when time of system start is programmed.
Dip switch
DS3
Heating
Speed Tap
A
—
—
OFF
OFF
B
—
—
ON
OFF
C
—
—
OFF
ON
D
—
—
ON
ON
Mode
No.
First
Code
No.
Setting Contents
Second Code No.
01
02
03
04
05
06
07
08
09
10
11
12
13 14 15
10
(20)
0
Filter contamination
2500 hr
1250 hr
—
—
—
—
—
—
—
—
—
—
— — —
3
Display time to clean
air filter calculation
Display
No
display
—
—
—
—
—
—
—
—
—
—
— — —
12
(22)
1
External ON/OFF
input
Forced
OFF
ON/OFF
control
—
—
—
—
—
—
—
—
—
—
— — —
5
Power failure
automatic reset
Not
equipped
Equipped
—
—
—
—
—
—
—
—
—
—
— — —
14
(24)
3
Discharge pipe
temperature
(cooling)
°C
13
14
15
16
17
18
19
20
21
22
23
24
25
°F
55.4
57.2
59 60.8 62.6
64.4
66.2 68 69.8 71.6 73.4 75.2
77
4
Discharge pipe
temperature
(heating)
°C
18
19
20
21
22
23
24
25
26
27
28
29
30
°F
64.4
66.2
68 69.8 71.6 73.4 75.2
77
78.8 80.6 82.4 84.2
86
Contents of Control Modes
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...