Field Settings for Outdoor Unit
SiUS342004EB
179
Part 5 Field Settings and Test Operation
35
Outdoor > 40 m
(130 ft) below
indoor
To increase Tc target heating.
2.
3
5
Level > 40 m (130 ft)
Level max. 40 m (130 ft)
Do not use
0
1
~
7
37
Heat pump
lockout 2
Used for heat pump lockout
2.
3
7
OFF
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
0
1
2
3
4
5
6
38
Emergency
operation
(master)
To prohibit a compressor or
complete in “Master”. Since
module is permanent disabled,
immediately replace the defective
component(s).
2.
3
8
OFF
Master unit OFF
0
3
39
Emergency
operation (slave
1)
To prohibit a compressor or
complete “Slave 1”. Since module
is permanent disabled, immediately
replace the defective
component(s).
2.
3
9
OFF
Slave 1 unit OFF
0
3
40
Emergency
operation (slave
2)
To prohibit a compressor or
complete “Slave 2”. Since module
is permanent disabled, immediately
replace the defective
component(s).
2.
4
0
OFF
Slave 2 unit OFF
0
3
42
Outdoor fan
Outdoor fan noise countermeasure
(limit fan speed).
2.
4
2
Standard
Mode A
Mode B
0
1
2
49
Outdoor > 50 m
(164 ft) above
indoor
Height difference setting max. 90 m
(295 ft).
2.
4
9
Off (max. 50 m (164 ft))
On (max 90 m (295 ft))
0
1
51
Sequence multi
outdoor
Sequence addressing between
master and slave units.
2.
5
1
Automatic
Forced master
Forced slave 1
Forced slave 2
0
1
2
3
60 Gas furnace
setting
Used for gas furnace connection
2.
6
0
No gas furnace connection
Gas furnace connection
0
1
62
Cooling/Heating
capacity learning
control
Adjust cooling and heating capacity
learning control
2.
6
2
OFF
Cooling adjustment
Heating adjustment
Cooling and heating
adjustment
0
1
2
3
64
Phased
installation
setting
Used to make setting for phased
installation.
2.
6
4
OFF
Single module to dual module
installation
Dual module to triple module
installation
0
1
2
78
Heat pump
lockout
temperature
Heat pump is locked out when the
outdoor air temperature is smaller
than the heat pump lockout
temperature.
2.
7
8
–26.1°C (–15°F)
–23.3°C (–10°F)
–20.5°C (–5°F)
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
Forced heat pump lockout
1
1
1
1
1
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...