SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
238
Reference
3.7.2 Indoor Fan Motor Abnormality (FXDQ-M, FXHQ-M Models)
Applicable
Models
FXDQ-M, FXHQ-M
Error Code
A6
Method of Error
Detection
This error is detected if there is no revolution detection signal output from the fan motor.
Error Decision
Conditions
When no revolutions can be detected even at the maximum output voltage to the fan
Supposed
Causes
Defective indoor fan motor
Broken wires
Defective contact
Troubleshooting
CHECK 16
Refer to page 372.
NO
YES
YES
Is the X4A
connector sec
u
rely
connected?
NO
Is
the
power of 12
VDC s
u
pplied
b
etween the Pins 1
and 3 when the X4A is
disconnected and the
power s
u
pply
t
u
rns ON?
Replace the indoor
u
nit control
PCB (A1P).
Properly connect the
connectors.
(At this time, check for any
defecti
v
e connector contact or
b
roken wires.)
Check the indoor fan motor
(M1F) and the wiring circ
u
its of
the motor.
CHECK 16
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...