Field Settings for Outdoor Unit
SiUS342004EB
169
Part 5 Field Settings and Test Operation
(1) Microcomputer normal monitor
This monitor blinks while in normal control, and turns ON or OFF when an error occurs.
(2) Segment display
Used to check the transmission and display the transmission state between indoor and outdoor
units, the contents of error, and the contents of field setting.
(3) BS button
Used to change mode.
(4) DIP switch
Used to make field settings.
The figure below shows the required position of the DIP switches on spare PCB. Change DIP
switches at time of power disconnected.
Application model The setting method (
represents the position of switches)
RXYQ72XA
RXYQ72XB
Set DS2-2 to ON.
RXYQ96XA
RXYQ96XB
Set DS2-1 and DS2-2 to ON.
RXYQ120XA
RXYQ120XB
Set DS2-3 to ON.
RXYQ144XA
RXYQ144XB
Set DS2-2 and DS2-3 to ON.
RXYQ168XA
RXYQ168XB
Set DS2-1, DS2-2 and DS2-3 to ON.
1 2 3 4
1 2 3 4
ON
OFF
DS1
DS2
1 2 3 4
1 2 3 4
ON
OFF
DS1
DS2
1 2 3 4
1 2 3 4
ON
OFF
DS1
DS2
1 2 3 4
1 2 3 4
ON
OFF
DS1
DS2
1 2 3 4
1 2 3 4
ON
OFF
DS1
DS2
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...