Field Settings for Outdoor Unit
SiUS342004EB
187
Part 5 Field Settings and Test Operation
Operation
sound
Rated
Level 1
Level 2
Level 3
Time set with "Night-time low
noise operation start setting"
Low noise mode
instructing
Operation sound set with
"External low noise setting"
10:00 PM
8:00 PM
12:00 AM
6:00 AM 7:00 AM 8:00 AM
Set with "Night-time low noise operation start
setting". (Factory setting is "10:00 PM".)
Set with "Night-time low noise operation end
setting". (Factory setting is "8:00 AM".)
*
Low noise
mode instructing
*
Operation sound set with
"External low noise setting"
*
Night-time
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
Time set with "Night-time low
noise operation end setting"
*
Operation sound mode
set with "Night-time low
noise operation setting"
[2-30]:
Power consumption limitation level (step 1) via the external control adaptor
(DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 1. The level is according to the table.
Default value: 3
Change [2-30]: 1, 2, 3, 4, 5, 6, 7, or 8 in function of required limitation
Value
[2-30]
Power consumption limitation (approximately)
1
60%
2
65%
3 (default)
70%
4
75%
5
80%
6
85%
7
90%
8
95%
[2-31]:
Power consumption limitation level (step 2) via the external control adaptor
(DTA104A61/62)
If the system needs to run under power consumption limitation conditions when an
external signal is sent to the unit, this setting defines the level power consumption
limitation that will be applied for step 2. The level is according to the table.
Default value: 1
Change [2-31] to 1, 2 or 3 in function of required limitation.
Value
[2-31]
Power consumption limitation (approximately)
1 (default)
40%
2
50%
3
55%
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...