Troubleshooting by Error Code
SiUS342004EB
281
Part 6 Service Diagnosis
3.31 Outdoor Unit Main PCB Abnormality
Applicable
Models
All outdoor unit models
Error Code
E1
Method of Error
Detection
Abnormality is detected under the communication conditions in the hardware section between the
indoor unit and outdoor unit.
Error Decision
Conditions
When the communication conditions in the hardware section between the indoor unit and the
outdoor unit are not normal.
Supposed
Causes
Defective outdoor unit main PCB (A1P)
Defective connection communication line between indoor and outdoor units
Troubleshooting
Return to normal?
YES
External factor other than
error (for example, noise
etc.).
Connect the communication
line correctly.
Replace the outdoor unit
main PCB (A1P).
N
O
N
O
Check if
inside/outdoor
relay
w
ires of outdoor
unit main PCB is
disconnected.
YES
Turn OFF the po
w
er once and
turn O
N
again.
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...