Troubleshooting by Error Code
SiUS342004EB
219
Part 6 Service Diagnosis
3.2 Error Codes (Sub Codes)
If an error code like the one shown below is displayed when a wired remote controller is in use,
make a detailed diagnosis or a diagnosis of the relevant unit.
3.2.1 Indoor Unit
Error code
Troubleshooting
Error Description
Diagnosis
A0 - 01
External protection device abnormality
Refer to page 230.
A6 - 01
Fan motor locked
A locked fan motor current has been detected.
Turn the fan by hand to check for the connection of
connectors.
A6 - 10
Fan overcurrent error
A fan motor overcurrent has been detected.
Check for the connection of the connector between the fan
motor and the fan PCB. If the connection is normal, replace
the fan motor. If this still cannot solve the error, replace the
fan PCB.
A6 - 11
Fan position detection error
An error in the detection of position of the fan motor. Check
for the connection of the connector between the fan motor
and the fan PCB. If the connection is normal, replace the
fan motor. If this still cannot solve the error, replace the fan
PCB.
A6 - 20
Indoor fan motor status abnormality
Refer to page 244.
A6 - 21
Low indoor airflow
Refer to page 245.
A8 - 01
Power supply voltage error
Check for the input voltage of the fan motor.
A9 - 01
Electronic expansion valve error
There is an error in the electronic expansion valve coil or a
connector disconnected.
A9 - 02
Refrigerant leakage detection error
Refrigerant leaks even if the electronic expansion valve is
closed. Replace the electronic expansion valve.
AA - 03
Gas furnace abnormality
Refer to page 251.
AH - 03
Transmission error (between the self-cleaning decoration
panel and the indoor unit)
(when the self-cleaning decoration panel is mounted)
Check for the connection of the harness connector
between the panel PCB and the indoor unit PCB.
AH - 04
Dust detection sensor error
(when the self-cleaning decoration panel is mounted)
Check for the connections of the connector X12A on the
panel PCB and the connectors X18A and X19A on the
sensor PCB.
AH - 05
Dust collection sign error
(when the self-cleaning decoration panel is mounted)
Check for clogging with dust at the dust collection port as
well as in the brush unit, S-shaped pipe, and dust box.
Furthermore, check for any stains of the light receiving and
emitting parts of the infrared unit.
AH - 06
Air filter rotation error
(when the self-cleaning decoration panel is mounted)
Check for anything getting in the way of rotating the filter
(e.g. the filter comes off or the drive gear is clogged with
foreign matter).
AH - 07
Damper rotation error
(when the self-cleaning decoration panel is mounted)
The damper does not rotate normally. Check for any
foreign matter around the damper and for the operation of
the gear and limit switch.
AH - 08
Filter auto clean operation error
(when the self-cleaning decoration panel is mounted)
The unit has not yet completed the filter self-cleaning
operation even after the lapse of specified period of time.
Check for any external noise, etc.
AH - 09
Filter auto clean operation start disabled error
(when the self-cleaning decoration panel is mounted)
The unit has been put into a state in which the filter self-
cleaning operation is disabled. Check the unit for the
operating conditions.
AJ - 01
Capacity setting error
There is an error in the capacity setting of the indoor unit
PCB.
AJ - 02
Electronic expansion valve setting error
There is a fault in the setting of the gear type electronic
expansion valve/direct acting type electronic expansion
valve.
C1 - 01
Transmission abnormality between indoor unit PCB and
fan PCB
Check for the conditions of transmission between the
indoor unit PCB and the fan PCB.
C1 - 07
Blower motor communication error
Refer to page 267.
C1 - 08
Climate Talk Communication error
Refer to page 268.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...