Troubleshooting by Error Code
SiUS342004EB
233
Part 6 Service Diagnosis
Note(s)
Check the drain piping for
clogging or upward slope, etc.
Replace the indoor unit control
PCB (A1P).
Replace the drain pump (M1P)
or check for dirt, etc.
YES
YES
NO
NO
The drain
pump works when the
power supply is reset for the
indoor unit.
The
voltage of
drain pump
terminals (
2) is in
accordance to the criteria
(
3) (within 5 minutes of
resetting the power
supply).
A
Model
1: Float switch (S1L) /
short circuit connector
2: Drain pump (M1P)
connector
3: Drain pump (M1P)
voltage
Note
FXFQ-AA
X15A
X25A
13 VDC
—
FXFQ-T
X15A
X10A
13 VDC
—
FXZQ-TA
X15A
X102A
13 VDC
—
FXZQ-TB
X15A
X25A
13 VDC
—
FXUQ-P
X15A
X25A
13 VDC
—
FXUQ-PA
X15A
X25A
13 VDC
—
FXEQ-P
X15A
X25A
13 VDC
—
FXDQ-M
X8A
X25A
220-240 VAC
—
FXSQ-TA
X15A
X25A
13 VDC
—
FXSQ-TB
X15A
X25A
13 VDC
—
FXMQ-PB
X15A
X25A
220-240 VAC
—
FXMQ-TB
X15A
X25A
13 VDC
—
FXMQ-TA
X15A
X25A
13 VDC
Option
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...