3.17 Drain Level above Limit
Applicable
Models
FXFQ-AA, FXFQ-T, FXZQ-TA, FXZQ-TB, FXUQ-P, FXUQ-PA, FXEQ-P, FXDQ-M, FXSQ-TA,
FXSQ-TB, FXMQ-PB, FXMQ-TB, FXMQ-TA (Option)
Error Code
AF
Method of Error
Detection
Water leakage is detected based on float switch ON/OFF operation while the compressor is not in
operation.
Error Decision
Conditions
When the float switch changes from ON to OFF while the compressor is not in operation.
Error code is displayed but the system operates continuously.
Supposed
Causes
Humidifier unit (optional accessory) leaking
Defective drain pipe (upward slope, etc.)
Defective indoor unit control PCB
Troubleshooting
Modify the drain piping.
YES
YES
N
O
Field
drain piping
has a defect such as
up
w
ard sloping.
N
O
A
humidifier
unit (optional
accessory) is installed
on the indoor
unit.
Defective indoor unit control
PCB (A1P).
Check if the humidifier unit is
leaking.
Caution
Be sure to turn off the po
w
er s
w
itch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...