SiUS342004EB
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
178
28
Power transistor
check
Used to troubleshoot DC
compressor. Inverter waveforms
are output without wire connections
to the compressor. It is useful to
determine whether the relevant
trouble has resulted from the
compressor or inverter PCB.
2.
2
8
OFF
ON (10 Hz)
0
1
29
Capacity priority
setting
Cancel the low noise level control if
capacity is required while low noise
operation or night-time low noise
operation is in progress.
2.
2
9
OFF
ON
0
1
30
Demand 1
setting
Used to make a change to the
targeted power consumption level
when the demand 1 control signal
is inputted.
2.
3
0
Level 1 (60%)
Level 2 (65%)
Level 3 (70%)
Level 4 (75%)
Level 5 (80%)
Level 6 (85%)
Level 7 (90%)
Level 8 (95%)
1
2
3
4
5
6
7
8
31
Demand 2
setting
Used to use a targeted power
current level when the demand 2
control signal is input.
2.
3
1
Level 1 (40%)
Level 2 (50%)
Level 3 (55%)
1
2
3
32
Normal demand
setting
Used to set permanent demand 1
or 2 control without inputting any
external signal.
2.
3
2
OFF
Demand 1 (2-30)
Demand 2 (2-31)
0
1
2
34
Indoor fan tap
setting
Indoor fan speed is limited to L tap
depending on connection capacity
and outdoor air temperature (Ta).
Indoor condition A:
Temperature
difference average of (indoor air
temperature – set temperature) is
less than 1.5°C (2.7°F).
Indoor condition B:
Temperature
difference average of (indoor air
temperature – set temperature) is
3°C (5.4°F) or more.
2.
3
4
Indoor capacity ≥ 130%
0
Indoor capacity ≥ 130% in
heating
1
Remote controller setting (Not
limited)
2
Limited in cooling when
Ta < 29.5°C (85.1°F) and
Indoor condition is in condition
A (
1)
Returned when
Ta > 32.5°C (90.5°F) or Indoor
condition is in condition B (
2)
3
Limited in cooling when
Ta < 23.5°C (74.3°F) and
Indoor condition is in condition
A (
1)
Returned when
Ta > 26.5°C (79.7°F) or Indoor
condition is in condition B (
2)
4
Limited in cooling when
Ta < 19.3°C (66.7°F) and
Indoor condition is in condition
A (
1)
Returned when
Ta > 22.3°C (72.1°F) or Indoor
condition is in condition B (
2)
5
Limited in cooling when
Ta < 29.5°C (85.1°F)
Returned when
Ta > 32.5°C (90.5°F)
6
Limited in cooling when
Ta < 23.5°C (74.3°F)
Returned when
Ta > 26.5°C (79.7°F)
7
Limited in cooling when
Ta < 19.3°C (66.7°F)
Returned when
Ta > 22.3°C (72.1°F)
8
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...