SiUS342004EB
Field Settings for Outdoor Unit
Part 5 Field Settings and Test Operation
168
Caution
2. Field Settings for Outdoor Unit
To continue the configuration of the
VRV
heat pump system, it is required to give some input to the
logic board of the unit. This chapter will describe how manual input is possible by operating the BS
buttons/DIP switches on the logic board and reading the feedback from the 7 segment displays.
For
VRV
heat pump system it is alternatively possible to make several commissioning field setting
through a personal computer interface (for this, option EKPCCAB1 is required). The installer can
prepare the configuration (off-site) on PC and afterwards upload the configuration to the system.
2.1 DIP Switch Setting when Mounting a Spare PCB
After replacement with spare PCB, be sure to make settings shown in the table on the following
page. The procedure for making settings of spare PCB is different from that used for factory
settings described above. Be sure to refer to the table shown on the following page in order to
make settings of spare PCB after replacement.
Enforce a re-initialization of communication: hold press the
RETURN (BS3)
button for minimum
5 seconds.
After initialization, a test operation is required from outdoor unit (hold the
SET (BS2)
button until
indication
t01
appears).
(3) BS
bu
tton (BS1~BS3)
(2) Segment display (SEG1~SEG3)
(4)
DIP switch
(DS1-1~4)
(DS2-1~4)
(1)
Microcomp
u
ter
normal monitor
(HAP)
Connection terminal
for transmission
u
se
ON
OFF
1 2 3 4
DS1
ON
OFF 1 2 3 4
DS2
Initial position
of DIP switches
Position
Set switch
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...