Special Control
SiUS342004EB
101
Part 4 Functions and Control
7.2.1 Oil Return Operation in Cooling
Oil return operation is not conducted before 2 hours have elapsed from the activation of power
supply.
After 2 hours have elapsed, oil return operation starts when the following item meets the
reference value.
Total amount of oil discharged from the compressor
(The total amount of oil discharged from the compressor is computed from Tc, Te, and
compressor loads.)
Oil return control starts every 8 hours of cumulative operation of the compressor, even if the
reference value is not met.
Part name
Electric symbol
Oil return operation
Compressor
M1C
Constant low pressure control
Fan motor
M1F, M2F
For heat exchanger mode
Electronic expansion valve
(Heat exchanger upper)
Y1E
Same as normal control
Electronic expansion valve
(Heat exchanger lower)
Y3E
Electronic expansion valve
(Subcooling heat exchanger)
Y2E
0 pulse
Electric expansion valve (Subcooling injection)
Y4E
760 pulse
Electronic expansion valve
(Refrigerant cooling)
Y5E
Same as normal control
Electronic expansion valve
(Receiver gas purge)
Y7E
0 pulse
Solenoid valve (Oil separator oil return)
Y1S
ON
Solenoid valve (Hot gas bypass)
Y2S
Same as normal control
Solenoid valve (Liquid shutoff)
Y3S
ON
Four way valve (HP/LP gas pipe)
Y4S
Hold
Four way valve (Heat exchanger lower)
Y5S
Hold
Four way valve (Heat exchanger upper)
Y6S
Hold
Solenoid valve (Accumulator oil return)
Y7S
Same as normal control
Ending condition
•
A lapse of 3 min
u
tes
•
TsA – Te < 3
°
C (5.4°F)
•
A lapse of 12 min
u
tes while the fre
qu
ency is
more than that of oil ret
u
rn operation.
&
OR
Indoor unit actuator
Oil return operation
Fan
Thermostat ON unit
Remote controller setting
Non-operating unit
OFF
Thermostat OFF unit
Remote controller setting
Electronic expansion valve
Thermostat ON unit
Normal control
Non-operating unit
224 pulse
Thermostat OFF unit
Forced thermostat ON (PI control)
Low-temperature hydrobox unit actuator
Oil return operation
Pump
Thermostat ON unit
Normal control
Non-operating unit
Normal control
Thermostat OFF unit
Normal control
Electronic expansion valve
Thermostat ON unit
Normal control
Non-operating unit
0 pulse
Thermostat OFF unit
Forced thermostat ON (PI control)
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...