SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
344
YES
NO
Replace the outdoor unit main PCB
(A1P).
Yes
Incorrect system setup.
Check if system is heat pump or
heat recovery.
Diagnosis Flowchart-5
Is there
any branch selector
unit connected?
NO
Was the
outdoor unit main
PCB replaced with
a spare PCB?
Replace the outdoor unit main PCB
(A1P).
YES
YES
NO
Is the
procurement of the
spare PCB proper?
Procure a proper spare PCB.
Error code
Sub code
UA-
29