Troubleshooting by Error Code
SiUS342004EB
239
Part 6 Service Diagnosis
3.7.3 Indoor Fan Motor Abnormality (FXSQ54TA, FXSQ54TB, FXMQ15-54PB,
FXMQ30-54TB, FXMQ-TA Models)
Applicable
Models
FXSQ54TA, FXSQ54TB, FXMQ15-54PB, FXMQ30-54TB, FXMQ-TA
Error Code
A6
Method of Error
Detection
Error from the current flow on the fan PCB
Error from the rotation speed of the fan motor in operation
Error from the position signal of the fan motor
Error from the current flow on the fan PCB when the fan motor starting operation
Error Decision
Conditions
An overcurrent flows.
The rotation speed is less than a certain level for 6 seconds.
A position error in the fan rotor continues for 5 seconds or more.
Supposed
Causes
Clogging of a foreign matter
Disconnection of the fan motor connectors (X1A and X2A)
Disconnection of the connectors between the indoor unit control PCB (A1P) and fan PCB (A2P)
Defective fan PCB (A2P)
Defective fan motor
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...