SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
240
Troubleshooting
The
fan motor
connectors (X1A
and X2A) of the fan PCB
(A2P) are
disconnected.
Remo
v
e the foreign matter.
YES
Connect the connector correctly.
YES
NO
The
connectors
b
etween the
indoor
u
nit control
PCB (A1P) and the fan
PCB (A2P) are
disconnected.
Connect the connector correctly.
YES
NO
The
f
u
se (F3U,
white) on the fan
PCB (A2P) has no
contin
u
ity.
Replace the fan PCB (A2P).
NO
Replace the indoor fan motor (M1F).
YES
NO
YES
The
fan can
b
e
mo
v
ed lightly
b
y
hand after the fan
motor connector of the
fan PCB (A2P) is
remo
v
ed.
Replace the indoor fan motor (M1F).
NO
YES
NO
YES
There is a
foreign matter aro
u
nd
the fan.
The
resistance
b
etween the
power wire terminals
of the fan motor and
motor frame (metal
part) is 1 M
Ω
or
b
elow.
T
u
rn OFF the power and
wait for 10 min
u
tes.
A
Remo
v
e the power wire
connector from the fan
motor and meas
u
re the
resistance
b
etween U
and V, V and W, and W
and U phases.
CHECK 16
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Go to the next page.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...