Troubleshooting by Error Code
Part 6 Service Diagnosis
218
Note(s)
1
: The system can keep operating, however, be sure to check and repair.
2
: The system may continue operation depending on the conditions.
3
: Regarding the error codes and descriptions of the low-temperature hydrobox (HXY-TA), refer
to the service manual SiUS392016EA.
Outdoor
Unit
J3
l
Discharge pipe thermistor (R21T) abnormality
Compressor body thermistor (R14T) abnormality
J5
l
Compressor suction thermistor (R12T) abnormality
Suction pipe thermistor (R10T) abnormality
J6
l
Heat exchanger deicer thermistor (R11T) abnormality
Heat exchanger gas pipe thermistor (R8T, R9T) abnormality
J7
l
Receiver inlet thermistor (R3T) abnormality
Subcooling heat exchanger liquid pipe thermistor (R7T) abnormality
Subcooling injection thermistor (R16T) abnormality
J8
l
Heat exchanger liquid pipe thermistor (R4T, R5T) abnormality
J9
l
Subcooling heat exchanger gas pipe thermistor (R6T) abnormality
Receiver gas purge thermistor (R13T) abnormality
JA
l
High pressure sensor abnormality
JC
l
Low pressure sensor abnormality
L1
l
Inverter PCB abnormality
L2
l
Momentary power failure during test operation
L4
l
Inverter radiation fin temperature rise abnormality
L5
l
Compressor instantaneous overcurrent
L8
l
Compressor overcurrent
L9
l
Compressor startup abnormality
LC
l
Transmission error between inverter PCB and outdoor unit main PCB
P1
l
Power supply voltage imbalance
P4 (
1)
l
Inverter radiation fin temperature abnormality
PJ
l
Field setting abnormality after replacing outdoor unit main PCB or combination of PCB
abnormality
System
U0 (
1)
k
Refrigerant shortage
U1
l
Reverse phase, Open phase
U2
l
Power supply insufficient or instantaneous abnormality
U3
l
Check operation not executed
U4
l
Transmission error between indoor units and outdoor units, open phase in power
supply wiring
U5
l
Transmission error between remote controller and indoor unit
U7
l
Transmission error between outdoor units
U8
l
Transmission error between main and sub remote controllers
U9
l
Transmission error between indoor units and outdoor units in the same system
UA
l
Improper combination of indoor unit and outdoor unit, indoor unit and remote
controller
Incorrect gas furnace connecting number
Incorrect electric heater capacity setting
UC (
1)
k
Address duplication of centralized controller
UE
l
Transmission error between centralized controller and indoor unit
UF
l
System not set yet
UH
l
System abnormality, refrigerant system address undefined
Climate Talk communication system combination error (before initial setting for
communication completes)
Climate Talk communication system combination error (after initial setting for
communication completes)
Error
code
Operation
lamp
Error contents
Reference
page
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...