Part 6 Service Diagnosis
360
Note(s)
4.3 Superheat Operation Check
CHECK 3
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points
Abnormal piping length
Bent or crashed pipe
(Including moisture choke)
Stop valve closed.
Defective valve coil
Defective valve body
Defective valve coil
Defective valve body
Are the coil resistance and insulation normal?
Refer to
CHECK 7 .
Does the piping length fall in the permissible range?
Conduct visual checks.
Eliminate moisture by vacuum operation. (Refer to
CHECK 8 .
)
Check if the stop valve is open.
Defective
discharge
pipe
temperature
control
Defective hot
gas bypass
control
Hot gas circuit clogging
Defective solenoid
valve coil
Defective solenoid
valve body
Defective outdoor unit
main PCB
Defective outdoor
unit main PCB
Defective valve coil
Defective low
pressure sensor
Defective subcooling
heat exchanger outlet
thermistor
Defective valve
body
Defective
injection
electronic
expansion
valve control
Superheat due to
shaft damage
Superheat due to
defective compressor
Defective indoor
unit electronic
expansion valve
Defective
control
Defective
control
Defective
outdoor unit
electronic
expansion valve
Defective four
way valve
operation
[In cooling only]
(
1)
Compressor
overheat
Refrigerant
shortage
High pipe
resistance
Defective
superheating
degree
control.
[In cooling]
If the indoor unit
electronic
expansion valve is
throttled too much:
(
2)
[In heating]
If the outdoor unit
electronic
expansion valve
excessively
throttled: (
3)
Temperature
increase of
discharge
pipe
Defective
injection
electronic
expansion
valve
Are the coil resistance and
insulation normal?
Is the connector properly connected?
Are the thermistor resistance characteristics
normal?
Are the voltage characteristics normal?
Is the pressure value checked with the
Service Checker corresponding to the
measurement value of the pressure sensor?
Check if the piping temperature connected
to the four way valve is normal.
Four way valve is in the
middle position.
Leak from hot gas bypass
valve
Defective
control
Defective thermistor for
indoor unit gas pipe
Defective thermistor for
indoor unit liquid pipe
Defective indoor
unit control PCB
Defective low pressure
sensor
Defective suction pipe
thermistor
Defective outdoor
unit main PCB
Are the voltage characteristics normal?
Is the pressure value checked with the Service
Checker corresponding to the measurement
value of the pressure sensor?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Are the coil resistance and insulation normal?
Are the coil resistance and insulation normal?
Is the connector properly connected?
Are the thermistor resistance characteristics normal?
1. Refer to Low pressure protection control for hot gas bypass control.
2. Superheating temperature control in cooling is conducted by indoor unit electronic expansion
valve.
3. Superheating temperature control in heating is conducted by outdoor unit electronic
expansion valve (main).
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...