Troubleshooting by Error Code
Part 6 Service Diagnosis
310
3.50.2 Inverter Radiation Fin Temperature Rise Abnormality (Fan PCB)
Applicable
Models
All outdoor unit models
Error Code
L4
Sub code: 06, 07, 18-21
Method of Error
Detection
Fan PCB radiation fin temperature is detected by the thermistor located inside the fan PCB circuit.
Error Decision
Conditions
Detected temperature exceeds a certain level.
Supposed
Causes
Radiation fin plate not fixed with screws
U0
error
Defective fan PCB
High outdoor air temperature
Troubleshooting
Continue operation.
Field factor. Radiation fin temperature
may have risen due to high outdoor air
temperature.
Turn ON the
power supply, and
then press the ON button.
Does the error
recur?
Replace the fan PCB (A5P, A6P).
YES
Rectify troubles.
Normal?
NO
Check for the cooling
conditions of radiation fin
used to cool the inverter.
(1) Is the radiation fin plate
fixed with screws?
(2) Error code
U0
is displayed
on the Error History
screen.
YES
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...