Troubleshooting by Error Code
SiUS342004EB
259
Part 6 Service Diagnosis
Note(s)
1. Temporary error code reset operation can be performed by pressing the push switch button
(BS2)
on the self-cleaning decoration panel PCB
2. For details on performing filter auto clean test operation, refer to the operation manual of the
self-cleaning decoration panel.
YES
NO
Normal.
Error
AH
recurs,
or the self-cleaning decoration panel
lamp (red) blinks?
The error could be caused by
other causes. Refer to other
diagnosis flowcharts in the
following order:
AH-05
→
03
→
04
→
07
→
08
→
09
.
Check the indoor unit control
PCB and self-cleaning
decoration panel PCB.
Start operation with remote
controller.
A
From the previous page
BS2
Electrical component
box (lid)
BS1