Field Settings for Indoor Unit
SiUS342004EB
141
Part 5 Field Settings and Test Operation
Note(s)
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however cannot
be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controllers, so they
cannot be set individually. Setting changes also cannot be checked.
3. Do not make settings other than those described above. Nothing is displayed for functions the
indoor unit is not equipped with.
4.
88
or
Checking the connection. Please stand by.
may be displayed to indicate the remote
controller is resetting when returning to the normal mode.
13 (23)
0
Ceiling height setting, Setting
of normal airflow
Standard
High ceiling 1
High ceiling 2
—
1
Airflow direction setting
4-direction
airflow
3-direction airflow
2-direction
airflow
—
2
Swing pattern settings
All direction
synchronized
swing
—
Facing
swing
—
4
Airflow direction adjustment
range
Draft prevention
Standard
Ceiling soiling
prevention
—
5
Setting of static pressure
selection
Refer to page on the right for details.
6
External static pressure
settings
Refer to page on the right for details.
14 (24)
4
Optional kit setting (UV lamp
+ humi economizer)
Refer to page on the right for details.
5
Dry mode set temperature
Room
temperature
Same as cooling
mode set
temperature
—
—
9
Mold proof operation setting
—
Standard
For high
humidity areas
—
11
Gas furnace test mode
OFF
Low heat
High heat
—
15 (25)
0
Drain pump operation setting
Refer to page on the right for details.
1
Humidification when heating
thermostat is OFF
Not equipped
Equipped
—
—
2
Direct duct connection
Not equipped
Equipped
—
—
3
Drain pump and humidifier
interlock selection
Not
interlocked
Interlocked
—
—
5
Individual ventilation setting
Normal
Individual
—
—
1b
4
Display of error codes on the
remote controller
—
Two-digit display
—
Four-digit
display
1c
0
Room temperature display
Not displayed
Displayed
—
—
1
Thermistor sensor for auto
changeover and setback
control by the remote
controller
Utilize the return
air thermistor
Utilize the
remote
controller
thermistor
—
—
3
Access permission level
setting
Level 2
Level 3
—
—
1e
2
Setback availability
N/A
Heat only
Cool only
Cool/heat
14
Setting restricted/permitted
for airflow block
Refer to page on the right for details.
Mode
No.
(Note 2)
First
Code
No.
Setting Contents
Second Code No.
Reference
Page
01
02
03
04
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...