Check
SiUS342004EB
363
Part 6 Service Diagnosis
4.5 Refrigerant Overcharge Check
CHECK 6
In case of
VRV
Systems, the only way to judge as the overcharge of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgment, refer to the information below.
Diagnosis of refrigerant overcharge
1. High pressure rises. Consequently, overload control is conducted to cause insufficient cooling
capacity.
2. The superheating degree of suction gas lowers (or wet operation is performed).
Consequently, the compressor becomes lower in discharge pipe temperature despite of
pressure loads.
3. The subcooling degree of condensate rises. Consequently, in heating, the temperature of
discharge air through the subcooled section becomes lower.
Cooling
High pressure
Lo
w
pressure
Frequency
High pressure
gradually rises
w
ith
increase in
frequency.
Subcooling degree
becomes higher.
(Liquid connection
pipe temperature
lo
w
ers.)
Lo
w
pressure rises due
to decreased
compressor output.
High pressure
Lo
w
pressure
Frequency
Heating
The outdoor unit electronic expansion valve
is closed due to the overload control.
Frequency comes to
the minimum level.
(
High pressure
is maintained
at a constant level.)
Lo
w
pressure
rises
due to
decreased
frequency.
To maintain
high pressure
,
frequency
decreases
under the
capacity control.
High pressure
drops or rises
immediately after the overload
control is complete.
Lo
w
pressure
drops due to
closed outdoor unit
electronic expansion valve.
Hot gas bypass is activated
for
lo
w
pressure
protection,
i.e., hunting at
lo
w
pressure
.
Higher degree of overcharge
(Degree of overcharge)
Proper amount
To maintain lo
w
pressure, frequency
increases under the capacity
control.
Frequency comes to
the minimum level.
High pressure
dropping control
(Lo
w
pressure is
maintained at a
constant level.)
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...