Troubleshooting by Error Code
SiUS342004EB
329
Part 6 Service Diagnosis
3.62 Transmission Error between Indoor Units and Outdoor
Units, Open Phase in Power Supply Wiring
Applicable
Models
All indoor unit models
All outdoor unit models
Error Code
U4
Method of Error
Detection
Microcomputer checks if transmission between indoor and outdoor units is normal.
Error Decision
Conditions
Transmission is not carried out normally for a certain amount of time.
Supposed
Causes
Open phase in power supply wiring
Short circuit in indoor-outdoor or outdoor-outdoor transmission wiring (F1/F2), or wrong wiring
Outdoor unit power supply is OFF
System address does not match
Defective indoor unit control PCB
Defective outdoor unit main PCB
Multi-tenant function is ON.