Special Control
SiUS342004EB
103
Part 4 Functions and Control
Note(s)
7.4 Outdoor Unit Rotation
In the case of multi outdoor unit system, this outdoor unit rotation prevents the compressor from
breaking down due to unbalanced oil level between outdoor units.
Details of outdoor unit rotation
In the case of multi outdoor unit system, each outdoor unit is given an operating priority for the
control.
The operating priority of outdoor units is changed by outdoor unit rotation. The outdoor unit rotation
prevents unbalanced oil level between outdoor units by eliminating the long stop of compressors
during partial load.
Timing of outdoor unit rotation
At the beginning of the startup control, or;
After oil return operation, or;
After defrost operation, or;
One of the outdoor units is stopped for 20 minutes or more (only in cooling).
Example) The following diagram shows outdoor unit rotation in combination of 3 outdoor units.
Master unit, slave unit 1 and slave unit 2 in this section are the names for installation. They are
determined in installation work, and not changed thereafter. (These names are different from
master unit and slave unit for control.)
The outdoor unit connected the control wires (F1 and F2) for the indoor unit should be designated
as master unit. Consequently, the LED displays on the outdoor unit main PCB for master unit, slave
unit 1 and slave unit 2 do not change.
Normal control
Normal control
Normal control
Normal control
Master Slave 1 Slave 2
Master Slave 1 Slave 2
Master Slave 1 Slave 2
Master Slave 1 Slave 2
A
A
Startup control
Outdoor unit
rotation
Outdoor unit
rotation
Outdoor unit
rotation
Priority
1
Priority
1
Priority
2
Priority
2
Priority
3
Priority
3
Priority
1
Priority
2
Priority
3
Priority
3
Priority
1
Priority
2
Oil return operation
or defrost operation
Any of outdoor
unit stops for a
period of 20
minutes or more.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...