SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
276
Note(s)
1. Infrared presence sensor PCB and connector
Diagnosis procedure 1
Infrared presence sensor
error (Error code
CE-01
)
Turn off the power and then reconnect.
Check infrared presence sensor output; refer to
sensor and address data No. 22-25.
Connect the connector correctly.
Connect the connector correctly.
NO
YES
YES
Is the
connection
of the connector
on infrared presence
sensor PCB and the
connector (
1)
normal?
NO
YES
YES
Is the
connection of the
sensor connector
normal?
Normal.
NO
Displays
15
by the above
verification
method.
Normal.
NO
Displays
CE-01
again or
15
for
sensor and
address data.
Replace the sensor.
Model
Infrared presence
sensor PCB
Connector
FXFQ-AA
A3P
X81A (A1P)
FXFQ-T
A4P
X2A (A2P)
FXZQ-TA
A5P
X110A (A6P)
FXZQ-TB
A5P
X81A (A1P)
FXUQ-P
A4P
X81A (A1P)
FXUQ-PA
A4P
X81A (A1P)
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...