SiUS342004EB
Specifications
Part 1 General Information
26
Model name (Combination unit)
RXYQ264XAYCA
RXYQ264XBYCA
Model name (Independent unit)
RXYQ120XAYCA
RXYQ144XAYCA
RXYQ120XBYCA
RXYQ144XBYCA
Power Supply
3 phase, 575 V, 60 Hz
1 Cooling Capacity
Nominal
Btu/h
(kW)
264,000 (77.4)
Rated
252,000 (73.9)
2 Heating Capacity
Nominal
Btu/h
(kW)
297,000 (87.0)
Rated
282,000 (82.6)
252,000 (73.9)
Casing Color
Ivory white (5Y7.5/1)
Dimensions: (H × W × D)
in (mm)
66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16
(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)
Heat Exchanger
Cross fin coil
Compressor
Type
Hermetically sealed scroll type
Displacement
m³/h
22.4 + 27.7
22.4 + 24.1
Number of Revolutions
r/min
6,606 + 5,214
6,606 + 4,536
Motor Output ×
Number of units
kW
6.9 × 1 + 8.0 × 1
6.9 × 1 + 6.9 × 1
Starting Method
Soft start
Fan
Type
Propeller fan
Motor output
kW
(0.7 × 2) × 2
Airflow rate
cfm
(m³/min)
7,989 + 9,480 (226 + 268)
Drive
Direct drive
Connecting pipes Liquid pipe
in (mm)
3/4 (19.1) C1220T (Brazing connection)
Gas pipe
in (mm)
1-3/8 (34.9) C1220T (Brazing connection)
Weight
lbs (kg)
727 + 793 (330 + 360)
Sound Pressure Level (Reference Data)
dB (A)
66.5 (68
3)
Sound Power Level (Reference Data)
dB
88
Safety Devices
High pressure switch, Fan driver overload protector, Overcurrent fuse,
Inverter overload protector, Leak detecting device
Defrost method
Deicer
Capacity Control
%
6-100
5-100
Refrigerant
Refrigerant Name
R-410A
Charge
lbs (kg)
25.8 + 25.8 (11.7 + 11.7)
Control
Electronic expansion valve
Standard Accessories
Installation manual, Operation manual, Connection pipes, Clamps
Drawing No.
3D122727
3D150058A
Notes:
1
2
3
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB)/Outdoor temp.: 95°FDB (35.0°CDB)/Rated capacity is certified under AHRI standard 1230.
Indoor temp.: 70°FDB (21.1°CDB)/Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB)/Rated capacity is certified under AHRI standard 1230.
Sound pressure level may increase during heating operation at ambient temps below 41°F (5°C) value in parenthesis is the max sound pressure at those conditions.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...