Field Settings for Indoor Unit
SiUS342004EB
151
Part 5 Field Settings and Test Operation
1.3.8 Electric Heater Setting (for FXTQ-TA, FXTQ-TB models)
: Factory setting
1.3.9 Electric Heater Capacity Setting (for FXTQ-TA, FXTQ-TB models)
Mode No. First Code No. Second Code
No.
Contents
Heater operation
Electric heater run for
defrost/oil return operation
11 (21)
3
01
Electric heater with heat
pump not allowed
Not allowed
02
Electric heater with heat pump
allowed
Not allowed
07
Electric heater with heat pump
not allowed
Allowed
08
Electric heater with heat pump
allowed
Allowed
: Factory setting
Model
Mode
No.
First
Code
No.
Second Code No.
01
02
03
04
05
06
07
08
09
10
Heater (kW)
No
heater
kit
3
5
6
8
10
15
19
20
25
FXTQ09TA
FXTQ09TB
11 (21)
5
h
h
h
—
—
—
—
—
—
—
FXTQ12TA
FXTQ12TB
h
h
h
h
—
—
—
—
—
—
FXTQ18TA
FXTQ18TB
h
h
h
h
h
h
—
—
—
—
FXTQ24TA
FXTQ24TB
h
h
h
h
h
h
—
—
—
—
FXTQ30TA
FXTQ30TB
h
h
h
h
h
h
—
—
—
—
FXTQ36TA
FXTQ36TB
h
h
h
h
h
h
—
—
—
—
FXTQ42TA
FXTQ42TB
h
—
h
h
h
h
h
h
—
—
FXTQ48TA
FXTQ48TB
h
—
h
h
h
h
h
h
—
—
FXTQ54TA
FXTQ54TB
h
—
h
h
h
h
h
—
h
h
FXTQ60TA
FXTQ60TB
h
—
h
h
h
h
h
—
h
h
h
—
: Available
: Not available
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...