Troubleshooting by Error Code
SiUS342004EB
283
Part 6 Service Diagnosis
3.33 Missing of Ground Leakage Detection Core
Applicable
Models
All outdoor unit models
Error Code
E2
Sub code: 06-08
Method of Error
Detection
Error is detected according to whether or not there is continuity across the connector X101A for
leakage detection circuit (Q1LD).
Error Decision
Conditions
No current flows at the time of turning ON the power supply.
Supposed
Causes
Disconnection of connector X101A
Wiring disconnection
Defective outdoor unit main PCB
Troubleshooting
NO
YES
YES
Is the system reset to
normal?
Is X101A connected?
The error is considered to have
resulted from external factors
other than failures (e.g. noise).
Turn OFF the power supply, and
then disconnect compressor leads.
YES
Properly connect the connector.
NO
Confirm if there is a
leakage with a Megger
tester.
Replace the outdoor unit main
PCB (A1P).
NO
Replace the compressor (M1C).
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Ensure the unit
corresponding to the error
code
E2
in monitor mode.
E2-06: Master
E2-07: Slave 1
E2-08: Slave 2
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...