Troubleshooting by Error Code
Part 6 Service Diagnosis
292
Troubleshooting
There are
I
oreign matter around the
applicable fan.
Remove the foreign matter.
YES
Check for the connections of all fan motor connectors. (
1)
NO
Turn OFF the power supply, and then wait for a period of 10 minutes.
Some connectors are
disconnected.
Insert the connector.
YES
NO
NO
There is a relay
connection error.
Correct the connection of the
relay harness.
YES
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
A
Check for any wire connection errors in 2 fan motors.
M1F: Connectors are white both on the PCB side and motor side.
M2F: Connectors are white on the PCB side and red on the motor side.
Check for Connection of Connector
Check for Colors of Connectors
There is no
continuity across the fuse
(F101U) on the fan
PCB.
Replace the fan PCB (A5P, A6P).
YES
NO
Outdoor units are equipped with 2 fan motors.
Check for M1F or M2F applicable to the error code
E7
while in
monitor mode of the outdoor unit.
Check in Monitor Mode
Go to the next page.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...