SiUS342004EB
Troubleshooting by Error Code
Part 6 Service Diagnosis
318
Note(s)
1. Connect and disconnect the connector once to ensure that it is securely connected.
Replace all of the inverter PCB (
2),
fan PCBs (
3), and noise filter PCBs
(
4).
YES
This is not the
LC
error.
Recheck the error code.
NO
YES
The
microcomputer
normal monitor indication
lamp (green) on the outdoor
unit main PCB (A1P)
is blinking.
Replace the inverter PCB (
2).
NO
NO
YES
The
microcomputer
normal monitor indication
lamp (green) on the outdoor
unit main PCB (A1P) is
blinking.
Properly connect the connector.
NO
YES
Is the
connector
between the outdoor
unit main PCB and the sub
PCB securely
connected?
Properly connect the connector X9A
(X10A) on the sub PCB option.
NO
Is the
normal operation
indication LED on the sub
PCB blinking?
YES
NO
Replace the outdoor unit main PCB
(A1P).
YES
The fuse of the
noise filter PCB has
blown out.
Continue operation.
The error could have resulted from
causes such as instantaneous
power failure.
The
LC
error recurs.
A
Inverter PCB (
2)
Fan PCB (
3)
Noise filter PCB (
4)
A4P
M1F: A6P
M2F: A5P
A2P, A3P
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...