Troubleshooting by Error Code
Part 6 Service Diagnosis
290
Note(s)
Reference
Reference
CHECK 4
Refer to page 362.
CHECK 12
Refer to page 369.
NO
YES
Are
the high
pressure and
ow pressure checked
by the service checker the
same as the actual measured
values of the high and
low pressure
sensors?
Replace the outdoor unit main
PCB (A1P).
NO
Replace the inverter PCB
(A4P).
CHECK 4
Is the power transistor
normal?
YES
Replace the compressor.
A
1. Make a comparison between voltage measured by the pressure sensor and that read by the
pressure gauge.
(The pressure sensor makes measurement of voltage at its connector block to convert it to
pressure.
CHECK 12
)