Troubleshooting by Error Code
SiUS342004EB
271
Part 6 Service Diagnosis
3.25 Capacity Setting Abnormality
Applicable
Models
FXMQ-TA
Error Code
C6-01
Method of Error
Detection
This error is detected by checking communication between the PCB (A1P) and the fan
microcomputer.
Error Decision
Conditions
Based on the communication data, decide whether the combination of capacity setting and the
type of fan driver is correct.
Supposed
Causes
Defective connection of the capacity setting adaptor
Wrong field setting
Troubleshooting
Is the indoor
u
nit PCB (A1P) replaced
b
y
the spare PCB?
After transmission
b
etween
the indoor and the o
u
tdoor
PCBs is esta
b
lished, perform
operation again and then
perform diagnosis again.
After transmission
b
etween
the indoor and the o
u
tdoor
PCBs is esta
b
lished, perform
operation again and then
perform diagnosis again.
Is a proper
capacity setting adaptor
installed when replaced
b
y the
space PCB?
Install a proper capacity
setting adaptor.
NO
NO
YES
YES
Caution
Be s
u
re to t
u
rn off the power switch
b
efore connecting or disconnecting
connectors, or parts may
b
e damaged.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...