Standby Control
Part 4 Functions and Control
84
3. Standby Control
3.1 Restart Standby
Used to forcedly stop the compressor for a period of 2 minutes, in order to prevent the frequent
ON/OFF of the compressor and equalize the pressure within the refrigerant system.
In addition, the outdoor fan carry out the residual operation for a while to accelerate pressure
equalizing and to suppress migration of the refrigerant to the evaporator.
3.2 Crankcase Heater Control
In order to prevent the refrigerant from migrating into the compressor oil in the stopped mode, this
mode is used to control the crankcase heater.
Crankcase heater
OFF
Crankcase heater
O
N
Discharge pipe
temperature < 70˚C (15
8
˚F)
Discharge pipe
temperature > 75˚C (167
˚F)