Field Settings for Outdoor Unit
SiUS342004EB
177
Part 5 Field Settings and Test Operation
2.5.2 Overview of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
0
COOL/HEAT
selection
Several systems as 1 zone change
over COOL/HEAT:
INDIVIDUAL:
VRV
indoor unit or
A-B-C input set mode.
MASTER: System is the
COOL/HEAT master unit.
SLAVE: System is not a
COOL/HEAT master.
2.
0
0
Individual
Unified Master
Unified slave
0
1
2
1
COOL/HEAT
unified address
Used to make address setting for
cool/heat unified operation.
2.
0
1
Address:
0
~
31
3
0
1
2
Low noise/
demand address
Used to make address setting for
low noise/ demand operation.
2.
0
2
Address:
0
~
31
3
0
1
5
Indoor fan forced
H
Used to force the fan of indoor unit
to H tap.
2.
0
5
Normal operation
Indoor fan H
0
1
6
Forced
thermostat
Used to force all indoor units to
operate forced thermostat ON.
2.
0
6
Normal operation
Forced thermostat ON
0
1
8
Te setting
Used to make setting of targeted
evaporating temperature for
cooling operation.
2.
0
8
Auto
6°C (42.8°F)
7°C (44.6°F)
8°C(46.4°F)
9°C(48.2°F)
10°C (50.0°F)
11°C (51.8°F)
0
2
3
4
5
6
7
9
Tc setting
Used to make setting of targeted
condensing temperature for
heating operation.
2.
0
9
Auto
41°C (105.8°F)
43°C (109.4°F)
46°C (114.8°F)
0
1
3
6
12
External low
noise setting/
demand setting
Used to receive external low noise
or demand signal.
2.
1
2
Input LNO/DE
NO
YES
0
1
13
AIRNET address Used to set address of AIRNET
2.
1
3
Address:
0
~
63
6
0
3
16 Heat pump
lockout 1
Used for heat pump lockout
2.
1
6
OFF
ON
0
1
18 High ESP setting
FAN
Fan high static pressure setting
2.
1
8
OFF
ON
0
1
20
Additional
refrigerant
charge
Used to perform additional
refrigerant charging operation
(compressor operation).
2.
2
0
Refrigerant charging
OFF
ON
0
1
21
Refrigerant
recovery and
vacuuming
Used to set the system to
refrigerant recovery mode (without
compressor run).
2.
2
1
Refrigerant recovery
OFF
ON
0
1
22
Automatic night-
time low noise
operation
Automatic night-time low noise
operation.
Time for the operation is subject to
the start and end time settings.
2.
2
2
OFF
Level 1
Level 2
Level 3
0
1
2
3
25
External low
noise level
Low noise level when the external
low noise signal is input at option
DTA104A61/62.
2.
2
5
Level 1
Level 2
Level 3
1
2
3
26
Automatic night-
time low noise
operation start
Time to start automatic “night-time
low noise” operation. (“Night-time
low noise” level setting should also
be made.)
2.
2
6
About 8:00 PM
About 10:00 PM
About 12:00 AM
1
2
3
27
Automatic night-
time low noise
operation stop
Time to stop automatic “night-time
low noise” operation. (“Night-time
low noise” level setting should also
be made.)
2.
2
7
About 6:00 AM
About 7:00 AM
About 8:00 AM
1
2
3
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...