SiUS342004EB
Field Settings for Indoor Unit
Part 5 Field Settings and Test Operation
154
1.3.15 Optional Accessories Output Selection
Using this setting,
operation output signal
and
abnormal output signal
can be provided. Output
signal is output between terminals X1 and X2 of adaptor for wiring, an optional accessory.
: Factory setting
1.3.16 External ON/OFF Input
This input is used for ON/OFF operation and protection device input from the outside. The input is
performed from the T1-T2 terminal of the operation terminal block in the electrical component box.
: Factory setting
1.3.17 Thermostat Differential Changeover
Differential value during thermostat ON/OFF control can be changed.
Factory Setting
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22)
0
01
Indoor unit thermostat ON/OFF signal is provided.
02
—
03
Output linked with ON/OFF of remote controller is provided.
04
In case of Error Display appears on the remote controller, output is
provided.
05
—
06
—
07
Only for FXSQ-TA, FXSQ-TB, FXMQ-PB, FXMQ-TB
Economizer (field supply) ON/OFF signal is provided.
Mode
No.
First Code
No.
Second
Code No.
Contents
12 (22)
1
01
ON: Forced stop (prohibition of using the remote controller)
OFF: Permission of using the remote controller
02
OFF
ON: Permission of operation
ON
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit indicates
A0
. The other
indoor units indicate
U9
.
04
—
05
Only for FXSQ-TA, FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
06
—
07
Only for FXSQ-TB, FXMQ-TB
ON: Economizer (field supply) is connected.
OFF: Not connected
F2 T1 T2
Forced stop
Input A
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
2
01
1°C (1.8°F)
02
0.5°C (0.9°F)
Model
Second Code No.
Contents
FXFQ-T, FXZQ-TA, FXUQ-P, FXEQ-P, FXSQ-TA, FXHQ-M,
FXTQ-TA, FXTQ-TB
01
1°C (1.8°F)
FXFQ-AA, FXZQ-TB, FXUQ-PA, FXDQ-M, FXSQ-TB,
FXMQ-PB, FXMQ-TB, FXMQ-TA, FXMQ-M, FXAQ-P,
FXLQ-M, FXNQ-M, FXMQ-MF, CXTQ-TA
02
0.5°C (0.9°F)
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...