Outline of Control (Indoor Unit)
SiUS342004EB
115
Part 4 Functions and Control
9.4.3 Thermostat Control with Operation Mode Set to AUTO
The system will conduct this temperature control shown below, only when the wireless remote
controller or any central remote controller is connected.
Furthermore, setting changes of the differential value (
D
) can be made.
: Factory setting
Mode
No.
First code
No.
Contents of setting
Second code No.
01
02
03
04
05
06
07
08
12
(22)
4
Automatic mode differential
0°C
0°F
1°C
1.8°F
2°C
3.6°F
3°C
5.4°F
4°C
7.2°F
5°C
9.0°F
6°C
10.8°F
7°C
12.6°F
Cooling thermostat ON
Cooling thermostat OFF
Heating thermostat ON
Heating thermostat OFF
(Ex.) When automatic cooling temperature is set to 27°C (80.6°F):
D
3°C (5.4°F)
2
D
(
+ 3.6)°F
2
D
(
+ 2)°C
Set cooling temperature
A
Set heating temperature
(
A
–
D
)
Display change
Cooling
Heating
Display change
Heating
Cooling
Differential value: 0°C (0°F)
30°C
(86°F)
Heating mode
Cooling mode
Control temp.
Differential value set to 1°C (1.8°F)
Set heating temp. Set cooling temp.
Heating mode
Control temp.
Differential value set to 2°C (3.6°F)
Heating mode
Control temp.
Differential value set to 3°C (5.4°F)
Heating mode
Cooling mode
Control temp.
Set heating temp. Set cooling temp.
Set heating temp. Set cooling temp.
Differential value set to 4°C (7.2°F)
Heating mode
Cooling mode
Control temp.
Differential value set to 5°C (9°F)
Set heating temp.
Set cooling temp.
Heating mode
Cooling mode
Control temp.
Differential value set to 6°C (10.8°F)
Heating mode
Cooling mode
Control temp.
Differential value set to 7°C (12.6°F)
Heating mode
Cooling mode
Control temp.
Set cooling temp.
Set cooling temp.
Set heating temp.
Set cooling temp.
Set cooling/ heating temp.
25°C
(77°F)
27°C
(80.6°F)
26°C
(78.8°F)
24.5°C
(76.1°F)
27°C
(80.6°F)
29°C
(84.2°F)
24°C
(75.2°F)
25°C
(77°F)
27°C
(80.6°F)
28°C
(82.4°F)
23.5°C
(74.3°F)
24°C
(75.2°F)
27°C
(80.6°F)
20°C
(68°F)
21.5°C
(70.7°F)
23°C
(73.4°F)
27°C
(80.6°F)
21°C
(69.8°F)
22°C
(71.6°F)
24°C
(75.2°F)
27°C
(80.6°F)
22°C
(71.6°F)
22.5°C
(72.5°F)
25°C
(77°F)
27°C
(80.6°F)
23°C
(73.4°F)
26°C
(78.8°F)
27°C
(80.6°F)
Cooling
mode
Cooling
mode
Set heating
temp.
Set heating
temp.
Summary of Contents for VRV RXYQ72-384XAYCA
Page 1: ...Service Manual RXYQ72 384XAYCA RXYQ72 384XBYCA Heat Pump 60 Hz SiUS342004EB...
Page 395: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 388 FXFQ07 09 12 15 18 24 30 36 48TVJU 3D086460B...
Page 397: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 390 FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 401: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 394 FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 402: ...Wiring Diagrams SiUS342004EB 395 Part 7 Appendix FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 409: ...SiUS342004EB Wiring Diagrams Part 7 Appendix 402 FXHQ12 24 36MVJU 3D048116C...
Page 410: ...Wiring Diagrams SiUS342004EB 403 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 418: ...Wiring Diagrams SiUS342004EB 411 Part 7 Appendix VAM1200GVJU 3D073270D...